Yes, Antifires fire rated glass systems are tested and certified to comply with the Turkish Regulation on Fire Protection of Buildings (BYKHY). The products meet the performance criteria outlined in TS 12633 and EN 1364-1, which are the primary standards referenced by the BYKHY for glazed elements. This includes compliance with both integrity (E) and insulation (I) requirements for various building classifications. For Sanliurfa public buildings, Antifires provides detailed technical documentation and test reports in Turkish, which can be submitted directly to local authorities to facilitate the approval process. The company’s product range, including EI30, EI60, and EI120 rated systems, offers solutions that align with the specific fire resistance levels mandated for different occupancy types under the BYKHY.
For hotel and hospital projects in Sanliurfa, an EI60 (60-minute integrity and insulation) rating is generally the minimum recommended standard, with EI120 often specified for critical areas such as fire escape stairwells and compartment walls separating high-risk zones. The Regulation on Fire Protection of Buildings (BYKHY) typically requires higher fire resistance levels for buildings with sleeping accommodation or limited mobility occupants. Antifires offers certified 28mm EI60 panels and 50mm/54mm EI120 systems that provide the necessary thermal barrier to prevent heat transfer and maintain safe egress conditions. The specific rating required should be confirmed by the project’s fire safety engineer based on the building’s height, fire load, and occupancy classification as defined in the local regulations.
Antifires ensures seismic compliance by designing its fire rated glass systems with flexible mounting details that accommodate building movement without compromising fire integrity. The framing systems utilize G.M.S. hollow steel sections with M6/M8 anchor bolts spaced at 300–600mm intervals, which are engineered to withstand lateral loads. The glass panes are set with ceramic wool gaskets (3mm–6mm thick) that allow for minor structural displacement while maintaining a tight seal. Furthermore, the intumescent seals within the frame are designed to activate only under fire conditions, ensuring they do not restrict normal building movement. Antifires provides installation guidelines that reference the Turkish Earthquake Code (TBDY 2018), ensuring that the glazed assemblies are integrated into the building’s primary structure in a manner that supports both seismic and fire safety performance objectives.